During the charging process, the amperage (current) flowing into the battery will decrease as it nears full charge:Current Decrease: Initially, the charger will provide a high current, which will gradually drop. When the current drops to a minimal level, it indicates a full charge.Built-in Meters: Some chargers come with built-in ammeters to display the current. Observing the current drop on these meters can help determine the charging status. [pdf]
Voltage Stability: As the battery charges, the voltage will increase. When the voltage levels off and stops rising, it indicates that the battery is fully charged. Voltage Meters: Use a digital voltmeter to monitor the battery voltage. A fully charged 12V lead-acid battery, for example, will read around 12.6 to 12.8 volts.
In addition to relying on the battery state of charge displays, you can confirm your solar batteries reach full charge by monitoring system performance over longer periods. Tools like solar charge controllers and inverters record data over time that reveals charging and discharging patterns.
During the charging process, the amperage (current) flowing into the battery will decrease as it nears full charge: Current Decrease: Initially, the charger will provide a high current, which will gradually drop. When the current drops to a minimal level, it indicates a full charge.
Step 3: Identity the fully charged LED: The controller should have a specific LED that indicates a fully charged battery. This is often the green or blue LED. Step 4: Assess the battery charge level: If the fully charged LED is illuminated, the battery is considered fully charged. If not, the battery needs more charging.
Voltage Meters: Use a digital voltmeter to monitor the battery voltage. A fully charged 12V lead-acid battery, for example, will read around 12.6 to 12.8 volts. This method requires some understanding of the specific battery type and its voltage characteristics.
The battery shall then be charged at a constant voltage of 14.6V while tapering the charge current. Charging will terminate when the charging current has tapered to a 0.02CA. Charge Time is approximately b7 hours. Safe Charging consists of temperatures between 32 ºF and 113 ºF.

What Size Circuit Breaker Should I Select for My Car Battery Configuration?Consider the total load amperage of your devices.Assess the wire gauge to determine the appropriate breaker size.Use a breaker size that allows for a 25% margin above the total load.Evaluate the type of circuit breaker: automatic vs. manual reset.Examine the vehicle’s electrical system and compatibility with existing components. [pdf]
Round the breakers up to next common size and you have600A vs 500A. If the battery cabinet design is only for capacity (meaning all cabinets must be on line to handle discharge) one could use 500A breaker, maybe even 450A in the scenario above. Sometimes it is requested that 600A be used however.
The highest voltage that may be applied over all end ports, the distribution type, and how the circuit breaker is completely integrated into the system all contribute to the overall voltage rating. It is essential to choose a circuit breaker with sufficient voltage capacity that corresponds to the end application.
The standard rating of a DC circuit breaker is 700A. The battery short-circuit current, per published data for the battery=14,750A. Therefore, the recommended circuit breaker in this example=700A, 65VDC, 15,000 AIC. Moving onto the conductor, we know the cable sizing current=1.25×533=666A.
Circuit Breaker Size: ? CB size should be rated at 125% of the circuit current. = 125% × 16 A = 1.25 × 16 A Required Circuit Breaker Size = 20A NEC 210.19 for continuous load circuits (Article 100) suggests that a 20-amp breaker should be used at 80% of its rated load for continuous circuits.
The battery circuit breaker sizing current = 1.25 x charging current = 1.25 × 400A =500A. The standard rating of DC circuit breaker is 500A. Therefore, the recommended circuit breaker in this example=500A, 65VDC, 10,000 AIC. Moving on to the conductor, we know the cable sizing current=1.25×400A=500A.
Circuit breakers are available in a variety of sizes and configurations. The highest voltage that may be applied over all end ports, the distribution type, and how the circuit breaker is completely integrated into the system all contribute to the overall voltage rating.

During discharge, sulfur from the sulfuric acid combines with lead to form lead sulfate while hydrogen combines with oxygen released at the positive plate to form water. This is given the formula below: During ch. . As the battery charging nears completion, the charge current is usually higher than the current required to break the. . Though hydrogen and oxygen gases are not as dangerous to breathe as hydrogen sulfide and sulfur dioxide gas, they are nevertheless dangerous in high concentrations as they can cause a fire. In all cases, the us. [pdf]
Ignition sources within close proximity (i.e. 1 -2 meters) may still cause an explosion due to localised concentrations of hydrogen gas escaping the battery housing. Ensure employees are aware of the risks of hydrogen gas through training, Safe Work Method Statements (SWMS) and promote the use of PPE during charging of the batteries.
If, instead of being used to charge the battery, an ampere-hour of charge is used completely to produce gas, it will create 0.01474 cubic feet, or 0.418 liters, of hydrogen per cell at standard temperature and pressure.
Overcharging, or lead acid battery malfunctions can produce hydrogen. In fact, if you look, there is almost always at least a little H2 around in areas where lead batteries are being charged. Overcharging, especially if the battery is old, heavily corroded or damaged can produce H2S.
And yes, I charge my car batteries in a well ventilated area so Hydrogen gas build-up is not an issue. It's he corrosive Hydrogen Sulfide gas that concerns me. Yes it can produce Hydrogen-Sulfide, but usually only if overcharged (which may be your case). There is a write-up at the Battery University Website which talks about it:
Normally, insignificant quantities of gases are released by a battery during the first part of the charge, as most of the charging current is used in charging the battery. Only during the last stages of the charge does the process become inefficient, so that an increasing portion of the current is used up by the creation of heat and gases.
Overcharging, especially if the battery is old, heavily corroded or damaged can produce H2S. Deteriorated, old or damaged lead acid batteries should be removed from service, as damaged batteries are much more likely to be associated with production of H2S.